基于倒塌延性的输电塔地震抗倒塌设计方法研究
DOI:
作者:
作者单位:

山东大学

作者简介:

通讯作者:

中图分类号:

TU 355.2

基金项目:

国家自然科学基金项目(面上项目,重点项目,重大项目)


Study on seismic collapse resistant design method of transmission tower based on collapse ductility
Author:
Affiliation:

Shandong University

Fund Project:

  • 摘要
  • |
  • 图/表
  • |
  • 访问统计
  • |
  • 参考文献
  • |
  • 相似文献
  • |
  • 引证文献
  • |
  • 资源附件
  • |
  • 文章评论
    摘要:

    通过开展倒塌延性分析,进而提出优化方案以调整结构抗侧刚度是提高地震下结构抗倒塌能力的常用方法,目前该方法多应用于建筑结构,而关于输电塔的抗倒塌研究尚未开展。因此,本文依托实际输电线路工程,基于ABAQUS软件建立了输电塔有限元模型,采用静力推覆分析(Pushover)和增量动力分析(IDA)方法,获得了输电塔倒塌延性;针对输电塔薄弱节间,提出了一种以杆件内外径之比为影响参数的输电塔地震抗倒塌优化设计方法,并通过有限元分析对优化效果进行了验证。结果表明,优化后的输电塔薄弱节间抗震性能最高可达70%,非薄弱节间优化效果也在10%左右,验证了该优化方法能有效提高输电塔抗倒塌性能,可为输电塔抗震设计提供指导。

    Abstract:

    It is a common method to improve the collapse resistance of structures under earthquakes by carrying out the collapse ductility analysis and proposing an optimization scheme to adjust the lateral stiffness of structures. At present, this method is mostly applied to building structures, and the research on the collapse resistance of transmission towers has not been carried out. Therefore, based on the actual transmission line project, this paper established the finite element model of transmission tower based on ABAQUS software, and obtained the collapse ductility of transmission tower by using Pushover analysis ( Pushover ) and incremental dynamic analysis ( IDA ) methods. For the weak sections of the transmission tower, an optimization design method for seismic collapse resistance of the transmission tower with the ratio of inner and outer diameters of the members as the influencing parameter is proposed, and the optimization effect is verified by finite element analysis. The results show that the seismic performance of the weak section of the optimized transmission tower can reach 70 %, and the optimization effect of the non-weak section is about 10 %, which verifies that the optimization method can effectively improve the collapse resistance of the transmission tower and provide guidance for the seismic design of the transmission tower.

    参考文献
    相似文献
    引证文献
引用本文
分享
文章指标
  • 点击次数:
  • 下载次数:
  • HTML阅读次数:
  • 引用次数:
历史
  • 收稿日期:2022-05-31
  • 最后修改日期:2022-07-26
  • 录用日期:2022-11-07
  • 在线发布日期:
  • 出版日期:
您是第位访问者
振动、测试与诊断 ® 2024 版权所有
技术支持:北京勤云科技发展有限公司